0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing

Product Details
Customization: Available
After-sales Service: 12 Months Warranty & Life-Time Sale Service
Warranty: 1 Year
Manufacturer/Factory, Trading Company
Gold Member Since 2023

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Quality Assurance
The supplier provides quality assurance
Raw-Materials Traceability
The supplier has traceability identification of raw materials
Standardized quality control
The supplier has a complete and standardized quality control process, check the Audit Report for more information
to see all verified strength labels (27)
  • 0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
  • 0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
  • 0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
  • 0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
  • 0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
  • 0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
Find Similar Products
  • Overview
  • Product Description
  • Product Parameters
  • Packaging & Shipping
  • Our Advantages
  • Company Profile
Overview

Basic Info.

Model NO.
HD-120Vseries
Test Region
Charge and Discharge
Application
Lithium-ion Battery
Customized
Customized
Input Power Supply
AC380V
Power Factor
≥99%(Full Load)
Charging Voltage Range
0V~1.0V
Discharging Voltage Range
150V~6V
Current Range
0~240A
Transport Package
Wooden Box
Specification
686mm X 730mm X 1470mm
Trademark
hongdian
Origin
China
HS Code
9030899090
Production Capacity
1000pieces/Year

Product Description

Product Description

This system can provide CC mode, CV mode, CCCV mode, Pulse mode, CP mode, CR mode, DCIR mode, and HPPC etc. Through the work step editor, they can be edited to work in a combined work mode and can be quickly switched on the user's requirements. Through these basic functions, the test system can carry out battery performance testing, rate charge and discharge testing, capacity testing, cycle life testing, DC internal resistance testing, reliability testing, energy efficiency testing, simulated road condition testing, etc. When the same device works with multiple channels, the channels are completely independent of each other; when there is a need to expand the current, the channels can be connected in parallel.
0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
 
Product Parameters

 

AC Input Parameters

Item Technical Parameters
Wiring Method AC380V Three-Phase Five-Wire System
Input Power Supply AC380V
Power Factor ≥99%(full load)
THDi ≤5%(full load)
Maximum feedback efficiency ≥92%(full load)

 

DC output parameters
Item Technical Parameters
Voltage range Charging Voltage: 0V ~ 150V Discharging Voltage: 6V ~ 150V
Voltage Accuracy ±0.05%FS
Voltage Resolution 1mV
Current Range 0 ~ 240A  (customized)
Current Accuracy ±0.05%FS
Current Resolution 1mA
Current Response Time 10ms(10%FS ~ 90%FS)
Charge/Discharge Conversion Time 20ms(-90%FS ~ 90%FS)
Channel Control Mode All channels can be independently controlled.
Auxiliary channels Each channel is equipped with an auxiliary temperature channel.

 

Step Function Features / Function Features of Operation Steps
Item Technical Parameters
Minimum Data Logging Time 10ms
Editable Number of Steps 2000
Number of Step Cycles 65535
Step Cycle Nesting 5
Charge and Discharge Modes Idle, Pause, Constant Current Charge (CC), Constant Voltage Charge (CV), Constant Resistance Charge (CR), Constant Current Constant Voltage Charge (CCCV), Constant Power Charge (CP), Constant Current Discharge (DC), Constant Power Discharge (DP), Constant Resistance Discharge (DR), Direct Current Internal Resistance Test (DCIR)
Termination Criteria Voltage, Current, Capacity, Energy, Time, Power, Cycle Count, BMS Parameters, Custom Advanced Parameters (Supporting Single or Multiple Logic AND/OR Combinations)
Execution Action Types Jump, Pause, Protect, Next Step
Importing DBC Files Supports File Editing, Saving, and Importing
Direct Current Internal Resistance Testing (DCIR) Supports DCIR (Direct Current Internal Resistance) test steps, hardware real-time calculation, and supports two types of tests: (V1-V2)/(I1-I2) and (V1-V2)/I.
Data Export Methods Export data in Excel and CSV formats.

 

Protection Functions
Item Technical Parameters
AC-Side Protection AC Grid Voltage Over/Under Voltage Protection, Surge Protection, Anti-Islanding Protection, Over/Under Frequency Protection, Hardware Overtemperature Protection, Self-Test Protection, etc.
DC-Side Protection Bus Over/Under Voltage Protection, Hardware Overtemperature Protection, Battery Channel Line Reverse Connection Protection, etc.
Battery-Side Comprehensive Protection Battery pack total voltage upper/lower limit protection, battery cell voltage upper/lower limit protection, battery temperature upper/lower limit protection, battery charge/discharge current upper limit protection, battery capacity upper/lower limit protection, BMS communication loss protection, network disconnection protection, etc.
Ingress Protection (IP) Rating IP22
Operating Temperature Range 0ºC~ 45ºC
Cooling Method Forced Air Cooling
Sound Level ≤75dB

 

Packaging & Shipping

 

0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
1.Standard exported package: Internal anti-collision protection, external export wooden box packaging.
2.Shipping by Fedex, by air, by sea according to customers' requirements to find the most suitable way,
3.Responsible for the damage during the shipping process will change the damage part for you for free.
4.Supply with the suitable voltage input and source plug according to your country requirements.
Our Advantages

1.BMS free docking development
2. Accuracy 0.05%
3. Charge and discharge efficiency 92%
4. Avant-garde voltage protection below 60v, without a protection board, our software can predict 7 volts in advance
5. Our chassis appearance design is exquisite, small, in line with the optimal solution to heat dissipation effect, while using Delta fan, IGBT Infineon, the best configuration to ensure heat dissipation effect
 
Company Profile

 

0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
Shenzhen Hongda New Energy Co., LTD., founded in 2014, is a supplier of new energy (energy storage) detection equipment and detection technology integrating research and development, production and sales. The company's "Hongdian" brand is committed to the research and development, production and sales of energy storage, power lithium battery pack aging detection equipment.

Over the years, the company's steady growth, office, production environment reached 6000 square meters. The company has energy saving feedback technology, battery management and control, battery system integration and other technologies. The company mainly serves energy storage, power and other lithium PACK manufacturers.

With the development of business, the company's products are constantly enriched, including energy storage, power lithium battery pack aging detection equipment, high voltage, high current, high power battery testing equipment, power battery pack, energy storage power station, mobile base station standby power supply and other new energy projects aging detection equipment.
  
0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
 
0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing
0V-150V 300A Multi-Voltage Battery Group Test System for Stationary, UPS, and Data Center Battery Testing

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now